  5. How To Configure the Grid: Simple Example

How To Configure the Grid: Simple Example

Because of the many different use cases of load balancing supported by Edge, the configuration can be a bit confusing. The configuration of the grid has been developed to be as intuitive as possible. Please read through the examples to make sure you understand the workflow before attempting to configure your own grid!

The Configuration of the grid will be explained using examples. Let’s continue with the example from the “installation” step. The grid has an installation current of 40A. The installation consists of 4 stations and an office building. The installation is protected using an energy meter GUARD

What do you need to get started?

 The “Live view” without any configuration done should look like this:


Video Instructions


Grid Configuration

To specify the grid and how load balancing should be done we will need to go to the grid configuration-tab. The following image shows what the grid will look like when you open it for the first time.

Every charge point and energy meter that is connected to Edge will be added to grid 0 by default. Grid 0 will have a default current of 16A.

Because every device is automatically added to grid 0 the only thing we need to change is the total current the grid can use. This is done in the following steps:

  1. Click the button: “Edit grid” on the right top of the screen.
  2. Click on “Grid 0 (Default)”.
  3. Change the setting “Max current” to 40A so it matches our example.
  4. Optional: Give this grid a user-friendly name by changing the “Grid Identifier” to e.g. “Office Parking”.
  5. Click the button: “Save changes”.

Configurable Options and Vocabulary

Here follows some information for all the options you will see during the config. Note that in 90% of the cases you will only have to configure the “Max current” and “Grid Identifier“, and leave the other settings untouched

  • Grid ID: This ID matches the Grid you just selected. This ID is unique for each grid and is used to identify them. Grid 0 is the default grid where every new device will be automatically added.
  • Grid Identifier: An optional user friendly custom name for the grid. This name will be shown in the overview instead of the Grid ID.
  • Guard Type: This read-only field notifies you how the grid is protected against overcurrent. It is automatically set based on the presence of an energy meter and it’s configuration. The possible options are:
    • Guard by energy meter: There is an energy meter configured as GUARD in this grid. The measurands from this energy meter are used to protect the grid.
    • Grid Limit: There is no energy meter configured as GUARD. There is no protection against overcurrent in case of charge point malfunction or external loads.
  • Max current: The maximum current that can be used by this grid. This current can be protected by using an energy meter as GUARD. Note that the current the charge points may consume can be more than “Max current” when there is a solar or battery installation in the same grid.
  • Max power: optionally, specify a second limit in watts. This is often used for contracted capacity. While “Max current” limits on the highest phase, “Max power” allows 3-phase imbalance. Also, it is possible to choose between active power(kW) and apparent power(kVA).  
  • Fuse Type(Max current): This setting can be used to configure how the Edge loadbalancer should deal with the (lowest) limit. 
    When a low number is chosen (soft limit, fuse), Edge will handle the limit in a agile way where Edge waits an extra second before responding when the limit is exceeded a little to filter out peeks/inrush load.  
    When choosing a higher number(conservative), Edge will respond faster when exceeding the limit and will take longer to ramp up again. Also, the loadbalancer will remember unregulated load peeks and use this as an extra margin. 
    The default configuration is “3. Fuse”, as this is strict enough to not cause problems, but allows some little peeks over the limit as a fuse is always made to handle short moments of over current. 
  • Hysteresis range: The Hysteresis is a percentage of the Max current where the algorithm will not try to increase or decrease the power of the grid. This gives a small blind spot where Edge will not change the setpoint. See the image at the bottom of this article for a visualization.
  • Panic threshold: The Panic threshold is a percentage above the Max current. When the current is between the Max current and the Panic current the algorithm will try to slow it down. When the current gets above the Panic current the algorithm will completely stop the entire grid once it gets reached. Be careful when selecting this value since a single current spike over this threshold will cause the grid to shut down and restart. See the image at the bottom of this article
  • Equalize energy mode: This setting determines how the priority between the charge points is divided, and thus how the power to the charge points will flow. The options are:
    • Off: Every charge point will have the same priority at any time.
    • Based on provided current (Default): The priority of the vehicles is determined based on how much power we made available for it (setpoint). The result is that if a vehicle does not use it provided current its priority will lower. At the end of the day every vehicle should have the same power provided to them.
    • Based on used current: The priority of the vehicles is determined based on how much power they have used. The result is that vehicles that are not using power will get a higher priority.
  • Enable solar charging: allows for the solar charging functionality. For more information see the article Solar charging.
  • Allow external charging profiles on charging stations: Edge will take external OCPP 1.6 charge profiles in account which are sent to the charge points. Edge will execute the charging profile, it might choose to charge slower as Edge keeps the protection of the grid as it’s first priority. an overview of the active profiles can be found and edited in the “Soft limits” tab.  
  • Allow external charging profiles on grids: OCPP 1.6: Charge profiles that are sent to the Edge itself will be applied to the grid. The external limit can be found and edited in the “Soft limits” tab. Contact LMS Support if you want to use this functionality. 

Simple example with the “Max current”, “Panic” and “Hysteresis” settings

Here follows a simple example with the “Max current”, “Panic” and “hysteresis” settings. In this example we will show the results for the default settings where only the “Max current” has been changed to 40A. The “panic” and “threshold” will both scale on the max current since they are percentages.